Space Charge and Electric Field Analysis on Contaminated XLPE Insulator M.H.A. Wahab; N. A. M. Jamail; E. Sulaiman; Q.E. Kamarudin; N.A. Othman; S.M.N.S. Othman
Indonesian Journal of Electrical Engineering and Computer Science Vol 12, No 1: October 2018
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijeecs.v12.i1.pp370-377

Abstract

Nowadays, XLPE cable has been widely used because it has better resistance than other cables. XLPE insulation has unique features including a high dielectric strength and high insulation resistance. A lot of researches based on hardware and software have been conducted to prove the effectiveness of XLPE cable such as AC and DC applications and Space Charge Distribution measurement under HVDC at High Temperature. This research focused on analysis of space charge and electric field on XLPE cable with effect of non-uniform contamination layer by using Quickfield Software. Non-uniform contaminations have been applied along XLPE cable using Arsenic Tribromide (AsBr3), Boron Bromide (BBr3), Ethylene Dichloride (CH2C1), Formic Acid (CH1O2), Formamide (CH3NO) and Alcohol element. Presence of these contamination elements represent of underground contamination. The size and layer of the contamination were non-uniform type. From the results, it is shown that lower dielectric constant of contamination will affect more on charge of XLPE insulation. As a conclusion, it can be seen lower dielectric constant value of contamination element greatly affecting the performance of XLPE insulation. Furthermore, size of contamination also influences the content of charge in contamination where the bigger the contamination size, the more charge contained in the contamination.
Breakdown Characteristic of Palm and Coconut Oil with Different Moisture N. A. M.Jamail; N. A. Azali; E. Sulaiman; Q.E. Kamarudin; S.M.N.S. Othman; M.S. Kamarudin
Indonesian Journal of Electrical Engineering and Computer Science Vol 12, No 1: October 2018
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijeecs.v12.i1.pp363-369

Abstract

Oils acts as insulation and cooling agent in the transformer. Petroleum-based oils are widely used in transformers due to their qualified properties as good insulation materials. Unfortunately, the used of petroleum-based oils has adverse effects on environment in the event of any failure to transformers such as tank leakage or explosions. Therefore, researchers have been studied and have found environmentally friendly oil that is suitable as substitutes in transformer. Thus, breakdown voltage tests using direct current and alternating current with the addition of different water content were performed to identify the potential of palm oil and coconut oil in the transformer isolation system. Refined, Bleached and Deodorized oil (RBDPO) and coconut oil samples were selected to be test in this study. The oil samples were test by varies the gap distance of test cell electrode and the level of water content. As a conclusion, RBDPO oil has greater breakdown voltage test under DC breakdown voltage test in term of increment of the gap distance.