Analisis Performansi Steam Turbine Generator 1 pada Power Plant 2 Utilities PT Pertamina RU V Balikpapan Gunawan -; Akhmad Nurdin; Ahmad Ria Saifuddin
Teknik Mesin "TEKNOLOGI" Vol 23, No 1 OKT (2022): Jurnal Teknik Mesin Teknologi
Publisher : Universitas Negeri Makassar

Show Abstract | Download Original | Original Source | Check in Google Scholar

Abstract

Energi listrik merupakan energi yang sangat dibutuhkan oleh semua orang pada saat ini. Terutama di kilang RU V Balikpapan, energi listrik digunakan sebagai penunjang operasional kilang. Energi listrik dihasilkan dari Generator yang digerakkan oleh Steam Turbine. Agar tidak terganggu operasional kilang yang sedang berlangsung, maka diperlukan penelitian tentang performansi Steam Turbine Generator. Penelitian mengenai performansi Steam Turbine Generator dilakukan di PT. Pertamina RU V Balikpapan, jl. Yos Sudarso No. 1 Balikpapan mulai September 2021 sampai Januari 2022. Nilai variabel bebas penelitian ini adalah pressure steam inlet dan temperature steam inlet. Sedangkan variabel terikat penelitian ini adalah nilai enthalpy dari steam inlet dan nilai efisiensi yang didapatkan. Dan untuk variabel kontrol penelitian ini adalah bukaan governor valve inlet steam. Berdasarkan hasil penelitian pertama bulan Desember 2020 diperoleh nilai efisiensi Steam Turbine Generator 1 pada minggu pertama 59,073 %, minggu kedua 53,692 %, minggu ketiga 60,449 %, minggu keempat 61,509 %. Untuk penelitian kedua pada bulan Desember 2021 nilai efisiensi yang diperoleh pada minggu pertama 61,564 %, minggu kedua 65,074%, minggu ketiga 62,429 %, minggu keempat 60,850 %. Bervariasinya nilai efisiensi diakibatkan perubahan daya listrik yang dihasilkan. Daya yang dihasilkan semakin mendekati nilai Most Economic Rating maka semakin besar nilai efisiensi yang didapatkan.
Analisis Performansi Pompa Offloading 50-PA-4501A pada Anjungan Main Stupa Puji Saksono; Akhmad Nurdin; Gilang Aditya
Journal of Applied Mechanical Engineering and Renewable Energy Vol 1 No 2: August 2021
Publisher : Indonesian Society of Applied Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (356.526 KB) | DOI: 10.52158/jamere.v1i2.222

Abstract

The activities of gas well exploitation have some problems. One of the problems is the amount of liquid (water) in the tubing column which obstructing the gas production. One of the ways to overcome the problem is to offload activity. One of the important equipment during offload activities is the offloading pump. An offloading pump is used to transfer liquid (water) from the well that has been collected in a vessel to the trunkline. This study aims to see the changes in the performance of the offloading pump between the initial conditions according to the manufacturer's specifications and the current condition after being used for ± 9 years. The type of pump being tested is a multi-stage centrifugal pump model 20 WUC-2R-19. The performance testing of offload pump is done by varying the discharge valve opening by 25%, 50%, 75%, and 100%. After that, compare the actual pump performance with the corrected data using the affinity law. The test performed during the offload process occur, and the fluid characteristics assume to be constant. The results showed that there was a decrease in performance between the initial operating conditions in 2011 with the actual conditions in 2020. The actual capacity of the pump decreased from 24 m3/h to be 23.45 m3/h. The efficiency of the offload pump decreased from the initial condition of 80% to 7.71%. The decrease in efficiency for 9 years is 2.29% or 0.25% per year.
Pengaruh Variasi Jumlah Sudu Terhadap Kinerja Turbin Hidrokinetik Tipe NACA0012 Akhmad Nurdin; Gunawan -; Ridwan Rasyid
Teknik Mesin "TEKNOLOGI" Vol 25, No 1 OKT (2023): Jurnal Teknik Mesin TEKNOLOGI
Publisher : Universitas Negeri Makassar

Show Abstract | Download Original | Original Source | Check in Google Scholar

Abstract

Energi hidrokinetik adalah energi listrik yang dihasilkan dari gerakan alami aliran sungai melalui perangkat elektromagnetik tanpa head yang memadai. Pada penelitian sebelumnya pemanfaatan aliran sungai hilir sebagai sumber energi listrik menggunakan turbin sumbu vertikal. Namun belum ditemukan penelitian yang mengkaji pengaruh jenis turbin dan jumlah sudu turbin hidrokinetik bersumbu horizontal yang digunakan langsung di sungai yang dalam. Penelitian ini bertujuan untuk mengkaji pengaruh perbedaan jumlah sudu turbin hidrokinetik pada sumbu horizontal yang digunakan langsung di sungai dalam untuk menghasilkan keluaran daya listrik yang optimal. Penelitian ini dilakukan secara eksperimental menggunakan turbin hidrokinetik dengan variasi 3 jenis sudu berdasarkan literatur dan penelitian sebelumnya. Data pengukuran yang dihasilkan pada kedalaman 1,2 meter untuk masing-masing jenis dikumpulkan. Data tersebut kemudian dianalisis dengan menggunakan Microsoft Excel. Turbin tipe NACA (jumlah sudu 3) menghasilkan Daya Mekanik Turbin(PT) terbesar sebesar 58,81 watt. Koefisien Daya Mekanik Turbin(Cp) terbesar yang dihasilkan adalah tipe NACA (jumlah sudu 3) yaitu sebesar 0,204. Sedangkan koefisien daya optimum sebesar 0,145 dan efisiensi turbin (ηT) yang optimum diperoleh tipe NACA 3 sebesar 14,9%. Turbin NACA yang menghasilkan kinerja optimal diberi nama RR001. Turbin NACA tipe RR001 dengan 3 sudu lebih optimal dalam menghasilkan Daya Mekanik Turbin(PT) dan koefisien daya (Cp) serta lebih efisien (ηT) bila dibandingkan dengan 2 sudu maupun 4 sudu.