1 X 1000 kVA Transformer Measurement Analysis using Dyn-11 Vector Group and Off Load Tap Changer

Setiyo Budiyanto (Department of Electrical Engineering, Faculty of Engineering, Universitas Mercu Buana)
Lukman Medriavin Silalahi (Department of Electrical Engineering, Faculty of Engineering, Universitas Mercu Buana)
Freddy Artadima Silaban (Department of Electrical Engineering, Faculty of Engineering, Universitas Mercu Buana)
Adi Kurnia (Department of Electrical Engineering, Faculty of Engineering, Universitas Mercu Buana)
Agus Dendi Rochendi (Department of Oceanographic physics, Lembaga Ilmu Pengetahuan Indonesia)
Muhammad Budi Haryono (Department of Materials Science and Engineering, Faculty of Engineering, Beijing Institute of Technology)
Mochamad Furqon Ismail (Department of Physical Oceanography, Geomar Helmholtz Centre for Ocean Research Kiel)



Article Info

Publish Date
25 Nov 2021

Abstract

The transmission line of electrical energy generated by the power plant is usually located far from the load center to be distributed to the community. The substation is part of a distribution transmission line that acts as a control center and consists of a collection of extra high voltage equipment. Routine maintenance of the power transformer as the main equipment of the substation must be scheduled so that its performance remains reliable. The proposed method of this research is to analyze the condition of the transformer through testing when it is off, to the calculation of the transformer ratio to determine the condition of the transformer windings using the calculation of the formula and measurement of the Raytech Transformer Turn Ration measuring instrument. In this research, the Raytech Transformer Turn Ratio measurement tool is used to determine the ratio of the winding input voltage of 20,000 volts and the output voltage of 400 volts on the power transformer. At a voltage of 40VAC, from the results of the comparisons that have been made, it can be seen that the test results of the Raytech Transformer Turn Ratio measuring instrument, if it crosses the 0.5% tolerance limit, the measurement results on one of the coils change the ratio. If the transformer is not regularly checked, the impact will result in unbalance of voltage on one of the coils. And one of the coils in phase will expand and cause a loss of voltage.