Simulasi Tegangan Lebih Akibat Sambaran Petir terhadap Penentuan Jarak Maksimum untuk Perlindungan Peralatan pada Gardu Induk

Ayu Sintianingrum (Department of Electrical Engineering Faculty of Engineering University of Lampung Jl. Sumantri Brojonegoro 1, Bandar Lampung)
Yul Martin (Unknown)
Endah Komalasari (Unknown)



Article Info

Publish Date
17 Jan 2016

Abstract

Intisari — Energi listrik merupakan faktor penting untuk menunjang kehidupan dan kegiatan masyarakat. Dalam proses penyaluran energi listrik dari gardu induk ke konsumen seringkali terjadi gangguan. Gangguan yang terjadi pada saluran transmisi dan distribusi salah satunya disebabkan oleh sambaran petir yang terjadi pada sistem tenaga listrik. Sambaran petir yang terjadi pada gardu induk akan menyebabkan kenaikan tegangan lebih yang besar pada peralatan di gardu induk. Untuk penentuan jarak maksimum arrester dilakukan dengan melakukan perhitungan yang selanjutnya dilakukan simulasi tegangan lebih akibat sambaran petir menggunakan software Alternative Transients Program (ATP). Simulasi dilakukan dengan memvariasikan arus petir yang menyambar serta waktu muka petir yang berbeda dan penentuan rating arrester dan jarak aman arrester dan transformator. Analisis dilakukan dengan melakukan perbandingan terhadap kedua waktu muka petir serta perubahan variasi arus petir. Dari hasil simulasi dan analisis diketahui bahwa perubahan waktu muka petir menyebabkan perbedaan perubahan tegangan yaitu tegangan pada waktu muka petir 1,2 μs lebih besar dibandingkan tegangan pada waktu muka petir 2 μs, hal ini dikarenakan waktu untuk mencapai puncak akan semakin cepat dengan semakin kecil waktu muka petir. Selain itu diperoleh perbandingan perubahan tegangan pada saat sebelum arester dan setelah melalui arester. Pada hasil penelitian ini diperoleh jarak maksimum arrester dan transformator yang disarankan yaitu sebesar 29,4 m. Kata kunci — arrester, alternative transients program (ATP), gardu induk, petir. Abstract — Electrical energy is an important factor for sustaining life and community activities. In the process of distribution of electrical energy from substations to consumers is often have a obstacle. The one of obstacle of the transmission lines and the distribution caused by lightning strikes occurring in the power system. Lightning strikes that occur in substations will cause a large increase overvoltage at the equipment in the substation. To determine the placement of arrester done by calculations and next doing overvoltage simulation of lightning strike using software Alternative Transients Program (ATP). Simulations doing by varying the flow of lightning striking and different front time of lightning also a safe maximum distance of arrester and transformer. The analysis was performed by a comparison of the two lightning  front time also the lightning current variation. From the simulation results and analysis showing that the lightning front time variation causing a voltage change which the voltage at the front time of 1.2 μs is higher than the voltage at the front time of 2 μs, this is because the time to reach the top will faster with a little lightning front time. Besides that, getting the result comparison of the voltage change before and after going through arrester. On the results of this study arrester and transformer maximum distance suggested is 29,4 m. Keywords— arrester, alternative transients program (ATP), substation, lightning.

Copyrights © 2016






Journal Info

Abbrev

ojs

Publisher

Subject

Control & Systems Engineering Electrical & Electronics Engineering Engineering

Description

Focus and Scope Publication of scientific research results in the field of electrical engineering which covers: ~ Power system analysis ~ Electrical energy conversion ~ High voltage technology ~ Electronics ~ Control system ~ Telecommunication system ~ Computer and interfacing ~ Information ...