Setrum : Sistem Kendali-Tenaga-elektronika-telekomunikasi-komputer
Vol 13, No 1 (2024): Edisi Juni 2024

Perbandingan Ketebalan Insulasi Jenis Kertas Laminasi Ditinjau dari Tegangan Tembus Transformator pada Dua Kondisi

Samsurizal, Samsurizal (Institut Teknologi PLN)
Afrianda, Rio (Institut Teknologi PLN)
Makkulau, Andi (Institut Teknologi PLN)



Article Info

Publish Date
01 Jun 2024

Abstract

An insulation layer is used to cover the transformer winding in a transformer. Commonly used insulations in transformers include oil insulation and paper insulation. Paper insulation is soft and flexible, adapting to any desired shape. The crucial factors to consider in insulation are strength and durability. This research was conducted through testing with two conditions: varying the thickness of the paper and the condition of the paper when dried and immersed in insulation oil. The test results show that insulation paper with a thickness of 1.04 mm in a dry state has an average breakdown voltage of 6.7 kV. When immersed in oil, the same thickness has a breakdown voltage of 23.82 kV, indicating that insulation paper with the immersion method has a better breakdown voltage than dry insulation paper.

Copyrights © 2024






Journal Info

Abbrev

jis

Publisher

Subject

Education

Description

SETRUM : Sistem Kendali Tenaga Elektronika Telekomunikasi Komputer merupakan jurnal yang diterbitkan oleh Jurusan Teknik Elektro, Fakultas Teknik, Universitas Sultan Ageng Tirtayasa (UNTIRTA) sejak 2012 menggunakan sistem Open Journal System ...