The screw compressor is the core component of the industrial refrigeration system at PT XYZ Majalengka, functioning to circulate and pressurize ammonia (NH3) refrigerant so that the heat-transfer process inside the cold-storage facility can run efficiently. Because the unit operates almost continuously, its reliability directly affects the temperature stability of the storage room and the quality of the food products handled by the company. This paper discusses the maintenance of the Yantai Moon LG20MYJA screw compressor, covering routine inspection, scheduled servicing, fault identification, and corrective action on the main components, namely the screw rotor, oil pump, joint coupling, lubrication system, and oil-cooling system. Data were obtained through direct field observation, analysis of the operational log sheet, and evaluation of mechanical condition and working parameters, particularly suction and discharge pressure. Observation shows that a rise in suction pressure from the normal setting of 0.30 bar to about 0.40 bar was traced to wear of the oil-pump joint coupling, which disturbed the compressor lubrication flow; replacing the joint coupling restored the suction pressure to its normal range. The results indicate that scheduled preventive maintenance combined with continuous monitoring of working parameters can prevent major failures, reduce the risk of downtime, and keep the compressor operating within its standard pressure and temperature limits, thereby supporting the production process at PT XYZ Majalengka.