Domestic wastewater is a major source of environmental pollution duo to its high contain of organic matter and nitrogenous compounds, such as Biological Oxygen Demand (BOD) and ammonia. This study aims to evaluate the effects of pH adjustment using sodium hydroxide (NaOH) and varying ozonation times on reducing BOD and ammonia levels in domestic wastewater. It also determines the optimal operating conditions needed to comply with the quality standards set by the Minister of Environment and Forestry Regulation No. P.11/Menlhk-Setjen/2025. Ozonation experiments were conducted on liquid domestic wastewater collected from Pujasera Puri Anyar. The fixed variables were set at a wastewater volume of 1.5 L, an ozone dose of 1,000 mg/h, and a temperature of 25°C. The independent variables included pH levels (7–9) and ozonation times (60–180 minutes), tested across 13 treatment combinations. The results showed the highest removal efficiency at pH 8.5 with 180 minutes of ozonation, yielding a BOD of 788 mg/L and an ammonia level of 2.5 mg/L. Optimal operating conditions were identified at pH 8.9 and 146 minutes of ozonation, with a desirability score of 0.848. Additionally, predictive modeling using a cubic model suggested that extending the treatment to pH 8.3 and 225 minutes could further reduce BOD and ammonia levels to 30 mg/L and 9.32 mg/L, respectively. Contribution to Sustainable Development Goals (SDGs):SDG 6: Clean Water and SanitationSDG 9: Industry, Innovation and InfrastructureSDG 12: Responsible Consumption and Production
Copyrights © 2027