Abstract

The reliability of electric power transmission systems is a crucial aspect in areas with high energy consumption such as Cilegon, which is predominantly supported by the industrial sector. The Cilegon Baru Substation (GI Cilegon Baru) plays a vital role as the main power transmission hub through the 150 kV transmission network, including a critical line connecting GI Cilegon Baru and GI Cilegon Lama with a combined configuration of Overhead Transmission Line (OHTL) and Underground Cable Transmission Line (UCTL). The differing characteristics of these two types of lines require an appropriate protection strategy to maintain power supply continuity. Based on operational data from 2020 to 2024, 71 disturbances were recorded on the 150 kV network of ULTG Cilegon, consisting of 68 temporary faults and three permanent faults in the form of broken conductors. To mitigate the impact of temporary faults, the auto-reclose function is implemented in the transmission line protection relay, which has proven effective in reducing outage duration and frequency, thereby improving overall system reliability. However, the implementation of auto-reclose on a combined OHTL–UCTL line requires special consideration due to differences in impedance, fault current characteristics, deionization processes, and circuit breaker capabilities. This study aims to analyze the implementation of auto-reclose on the 150 kV transmission line between GI Cilegon Baru and GI Cilegon Lama and to evaluate its impact on system reliability. The results of this research are expected to provide recommendations for optimal protection settings to enhance the stability and continuity of power transmission in the industrial area of Cilegon. Keywords: Auto-reclose, OHTL–UCTL, power system reliability, temporary faults, GI Cilegon Baru, GI Cilegon Lama.

Copyrights © 2026






Journal Info

Abbrev

energi-elektrik

Publisher

Subject

Computer Science & IT Control & Systems Engineering Electrical & Electronics Engineering Energy Engineering

Description

Jurnal Energi Elektrik ini adalah tempat untuk mempublikasikan hasil penelitian di bidang teknik elektro mengenai sistem tenaga listrik, telekomunikasi, sistem kendali, elektronika, komputer dan yang berhubungan dengan ...