Air-cooled condensers (ACCs) reject heat directly to the atmosphere, so operating-data fouling indicators are read against a heat sink that moves continuously. This study quantifies how much of the calculated fouling resistance of an ACC serving a 41.75 MW binary geothermal unit is generated by ambient-temperature variation alone, with the physical surface condition held unchanged, and establishes how that component depends on whether cooling-air flow is measured or inferred. A zone-resolved thermal model was built from bundle geometry, plant working-fluid states and a measured fan air velocity of 6.02 m s⁻¹, with n-pentane and air properties taken from CoolProp. The indicator was evaluated over the observed ambient range of 18.63 to 29.56 °C under three routes that differ only in which air-side quantity is measured. Ambient variation alone moved the indicator by 2.22 × 10⁻² m² K W⁻¹ across the mean daily range, which exceeded its own mean value by a factor of 3.3 and reversed its sign at 24.5 °C although the surface condition did not change. The negative values carry no physical meaning, because a deposit cannot reduce thermal resistance. The sign of the reported trend followed the air-side assumption rather than the equipment, and four clean-condition treatments shifted the level of the indicator without altering its ambient slope, which stayed negative in 100 % of 2,000 Monte Carlo samples. The calculated resistance therefore measures the ambient sensitivity of the method and not the fouling state of the bundle. Matched-ambient comparison bands, a plant-specific clean baseline and independent air-side indicators are required before it can support a cleaning or maintenance decision.