Analisis Ketidakseimbangan Beban terhadap Kerugian Daya pada Transformator Distribusi 20 kV Menggunakan Software ETAP Maulana Muslimin; Agung Trihasto; Deria Pravitasari; Andriyatna Agung Kurniawan
Jurnal Teknik Elektro dan Komputasi (ELKOM) Vol. 8 No. 1 (2026): Jurnal Teknik Elektro dan Komputasi (ELKOM)
Publisher : Universitas Muhammadiyah Jember

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.32528/elkom.v8i1.4948

Abstract

Abstract - Load imbalance in distribution transformers can lead to an increase in neutral current and power losses, thereby reducing the efficiency of the electric power distribution system. This condition was identified in six 20 kV distribution transformers on the SGN 04 feeder in Magelang, with initial load imbalance levels of 23.02% at M1-35A-2A, 22.7% at M1-44-26-4-A, 12.79% at M1-44-34, and the highest value of 54.33% at M1-44-9. This study aims to analyze the effect of load imbalance on neutral current and power losses and to evaluate the effectiveness of load balancing through inter-phase load relocation. The methods employed include load current measurements conducted over five days, symmetrical component calculations using GNU Octave, and Unbalanced Load Flow simulations using ETAP software to validate the calculation results. The results show that load imbalance has a significant impact on power losses, as indicated by an initial neutral current of up to 148.142 A at transformer M1-44-9 and power losses reaching 21.0245 kW. After load balancing was implemented, all transformers exhibited significant improvement, with load imbalance values reduced to below 3%, for example, M1-35A-2A decreased to 1.33%, M1-44-31 to 1.35%, and M1-44-9 to 0.45%. In addition, the neutral current was significantly reduced, such as at M1-44-9, where it decreased from 148.14 A to 11.84 A, and the remaining power losses were only in the range of 0.0068–0.1343 kW. Therefore, the load relocation strategy is proven to be effective in reducing load imbalance, neutral current, and power losses in accordance with SPLN 17:2014, while also improving the stability of the distribution system. Keywords : Load Imbalance, Distribution Transformer, Power Loss, ETAP, GNU Octave.
Perencanaan Perbaikan Faktor Daya Pada Industri Otomotif Muhammad Fachrul Reza; Deria Pravitasari; Agung Trihasto; Andriyatna Agung Kurniawan
Jurnal Teknik Elektro dan Komputasi (ELKOM) Vol. 8 No. 2 (2026): Jurnal Teknik Elektro dan Komputasi (ELKOM)
Publisher : Universitas Muhammadiyah Jember

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.32528/elkom.v8i2.4618

Abstract

Low of electrical power factor in industry increases power losses and loading still far from the available capacity has the potential to increase operational load. The objective of this research is to improve the power factor and to reduce power losses in all percentages of electrical system load at PT Putra Agung Setia using centralized capacitor bank. The method of research begins with an analysis of load profile data then creation of linear regression functions and alternative loading. Next, capacitor bank planning and power loss calculations are carried out. The results of research show that the lowest and highest loading percentage values when the system experiences power factor problems are 4.388% and 15.038%, then the linear regression model is obtained with the equation y = -1.9273 + 1.6188x. Linear regression model was created with baseline load profile. Alternative load scenarios were defined by 25%, 50%, 75%, and 100% higher than the highest baseline value. All alternative scenarios exhibited low power factor. The increase of power factor was carried out in percentage of loading at 4.388% to 100%. The reference target power factor improvement is set at 1. The results of Capacitor bank planning shows the need values of 2.5 kVAR, 5 kVAR, 10 kVAR, 20 kVAR, 40 kVAR, and 80 kVAR. The results of power factor improvement shows that the average power factor increases, while power losses decrease. The average power factor in the baseline and alternative scenarios increases to near 1, while power losses decrease to near 0 kW.