This article discusses the maintenance system for the Unit 1 condenser at PT PLN Nusantara Power UP Indramayu. The condenser is a crucial component in the steam power plant cycle, functioning to condense exhaust steam from the turbine into condensate water to maintain the plant's thermal efficiency. The primary focus of this report is to understand maintenance procedures and evaluate condenser performance efficiency based on operational field data. The methodology employed includes field observations, a literature review, and mass and heat balance calculations. Observations indicate that maintenance procedures are carried out in several stages, ranging from work document preparation and tube cleaning via the scrubbing method to leak detection. Based on the calculations, the actual condenser efficiency was recorded at 65.13%. This figure falls below the design efficiency standard of 80–100%, indicating a need for further maintenance on the heat transfer and vacuum systems to re-optimize the power generation unit's performance.