Analysis of Technical Loss Calculation Using Load Curve Approach on 20 kV Distribution Network Maulana, Rizky Rahmat; Salahuddin, S; Ezwarsyah, E; Ismail, Baharuddin; Shrestha, Ashish; Astonkar, Dhiraj Vijayrao
Journal of Renewable Energy, Electrical, and Computer Engineering Vol 1, No 2 (2021): September 2021
Publisher : Institute for Research and Community Service, Universitas Malikussaleh, Indonesia

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.29103/jreece.v1i2.5238

Abstract

Energy loss (losses) is the loss of a certain amount of energy generated when it is distributed to consumers so that it affects the profitability of the company concerned. The size of the losses from an electric power system shows the level of efficiency of the system, the lower the percentage of losses that occur the more efficient the system. Energy losses in the distribution network are generally divided into two, namely technical and non-technical losses. The calculation of technical losses in the 20 KV medium distribution network of PT PLN (Persero) Ulp Matang Glumpang Dua is carried out using the load curve approach method and using the help of the Microsoft Exel program, while the technical losses calculated are technical losses on the Medium Voltage Network and Distribution Transformer. From the results of the analysis of the calculation of technical losses in 2020, the total technical loss value at MG-01 Matang City is in the range of 13.8% to 20.8% which consists of the average technical loss in the Medium Voltage Network feeder of 0.02%. and the loss of Distribution Transformer by 17.6%.
Analysis of Technical Loss Calculation Using Load Curve Approach on 20 kV Distribution Network Maulana, Rizky Rahmat; Salahuddin, S; Ezwarsyah, E; Ismail, Baharuddin; Shrestha, Ashish; Astonkar, Dhiraj Vijayrao
Journal of Renewable Energy, Electrical, and Computer Engineering Vol. 1 No. 2 (2021): September 2021
Publisher : Institute for Research and Community Service (LPPM), Universitas Malikussaleh, Indonesia

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.29103/jreece.v1i2.5238

Abstract

Energy loss (losses) is the loss of a certain amount of energy generated when it is distributed to consumers so that it affects the profitability of the company concerned. The size of the losses from an electric power system shows the level of efficiency of the system, the lower the percentage of losses that occur the more efficient the system. Energy losses in the distribution network are generally divided into two, namely technical and non-technical losses. The calculation of technical losses in the 20 KV medium distribution network of PT PLN (Persero) Ulp Matang Glumpang Dua is carried out using the load curve approach method and using the help of the Microsoft Exel program, while the technical losses calculated are technical losses on the Medium Voltage Network and Distribution Transformer. From the results of the analysis of the calculation of technical losses in 2020, the total technical loss value at MG-01 Matang City is in the range of 13.8% to 20.8% which consists of the average technical loss in the Medium Voltage Network feeder of 0.02%. and the loss of Distribution Transformer by 17.6%.
Planning to Reconfigure the 150 kV Transmission Network at PT. PLN (Persero) Tualang Cut Network and Substation Hasibuan, Arnawan; Asran, Asran; Adriansyah, Fery; Ismail, Baharuddin; Siregar, Widyana Verawaty; Sayuti, Muhammad
Journal of Renewable Energy, Electrical, and Computer Engineering Vol. 3 No. 2 (2023): September 2023
Publisher : Institute for Research and Community Service (LPPM), Universitas Malikussaleh, Indonesia

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.29103/jreece.v3i2.11740

Abstract

System condition at PT. PLN (Persero) Tualang Cut Substation where the reliability of the 150 kV system depends on the Langsa Substation, which we will reconfigure on the Lgs-P.B and Lgs-T.C channels to P.B-T. C and T.C-Lgs. The planning for the reconfiguration of the 150 kv transmission network of the Tualang Cut Substation was carried out by estimating the distance of the transmission line and the constraints that occurred. The condition of the electric power system that is currently operating at PT. PLN (Persero) Tualang Cut Substation is considered less efficient in receiving power from the 150 kV SUTT interconnection. The SUTT in Tualang Cut currently receives electrical power from the Langsa Substation with a Losses value on lines 1 and 2 of 771,4142474 kW and experiences a Voltage Drop on lines 1 and 2 of 4,38 kV. After we reconfigured the channel, from the results of the reconfiguration there was a decrease in Losses on channels 1 and 2 by 311,298581 kW which before the reconfiguration of power losses on the line amounted to 771,4142474 kW and after being reconfigured to 460,1156668 kW there was a decrease in Voltage Drop on channels 1 and 2 by 1,44 kV, before the reconfiguration of the voltage drop on the line of 4,38 kV and after the reconfiguration to 2,94 kV, the reconfiguration carried out is the best solution to reduce losses and voltage drops.