Cellular Lightweight Concrete (CLC) offers potential for lightweight construction, while the incorporation of rice husk ash (RHA) may reduce cement consumption and promote agricultural waste utilization. However, the effectiveness of RHA may vary depending on mixture proportions. This study investigated the combined effects of RHA replacement and binder-to-natural sand (binder-to-NS) ratio on the mechanical, ultrasonic, and initial water absorption characteristics of CLC. RHA partially replaced Portland Composite Cement (PCC) at 0%, 5%, and 10% by mass of the binder, while binder-to-NS ratios of 1:2 and 1:3 were evaluated. Compressive strength was measured at 7 and 28 days, ultrasonic pulse velocity (UPV) at 28 days, and initial rate of absorption (IRA) at 7 and 28 days. At a binder-to-NS ratio of 1:2, 10% RHA increased the 28-day compressive strength to 4.54 MPa, approximately 90.0% above the control, increased UPV by 18.3% to 1.564 km/s, and reduced the 28-day IRA by 4.1% to 1.40 kg/m²/min. In contrast, at a ratio of 1:3, the same RHA replacement level reduced compressive strength and UPV by approximately 45.3% and 19.6%, respectively, while increasing IRA by 69.1%. Correlation analyses based on six mixture-level mean pairs at 28 days showed a strong positive association between compressive strength and UPV (r = 0.9253, R² = 0.8562, p = 0.0082) and a moderate negative but statistically non-significant association between compressive strength and IRA (r = −0.6712, R² = 0.4505, p = 0.1444). Within the investigated range, 10% RHA combined with a binder-to-NS ratio of 1:2 provided the most favorable overall performance among the RHA-containing mixtures.