Harmonic Mitigation with Active Filter in Coal Boiler Plant PT. Salim Ivomas Pratama Widagdo, Reza Sarwo; Andriawan, Aris Heri; Tauladan, Imam Suri
Jurnal ELEMENTER (Elektro dan Mesin Terapan) Vol 9 No 2 (2023): Jurnal Elektro dan Mesin Terapan (ELEMENTER)
Publisher : Politeknik Caltex Riau

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.35143/elementer.v9i2.6047

Abstract

Coal Boiler Plant at PT. Salim Ivomas Pratama is a plant for making steam, almost all activities in the cooking oil and margarine production process utilize electrical energy, such as submersible and centrifugal electric motors with controllers, computers, AC inverters, and many others which include non-linear loads. Electrical load whose correlation between voltage and current is unbalanced, this non-linear load will result in harmonic disturbances in the electric power system which causes a reduction in the service life of electrical equipment. Harmonics are defined as voltage and current frequency distortions that are not sinusoidal from pure frequencies. This study aims to determine how effective the active filter design simulated with the PSIM Software is in reducing harmonics with a non-linear load of 3 VSD connected to a 55 kW, 0.37 kW, and 7.5 kW induction motor. The results of measurements and analysis show that there are harmonics on the panel. SDP with a current harmonic value for phase R of 26.6%, phase S of 27.5%, and phase T of 25.5%, when compared with standard harmonics, all phases exceed the standard SPLN with a standard value of 20%. Then it is necessary to reduce harmonics with an active filter, after designing andsimulating it in the PSIM software the simulation results show that the current harmonics have changed for phase R by 3.3%, phase S by 4.0%, and phase T by 3,4 %. This shows that the design of the active filter is quite effective in mitigation a harmonic, to then be applied in practice at PT. Salim Ivomas Pratama in reduction the harmonics in a coal boiler plant.
Harmonic Mitigation in Microgrid to Improve Power Quality Widagdo, Reza Sarwo; Andriawan, Aris Heri; Hartayu, Ratna
Jurnal Teknologi Elektro Vol 15, No 1 (2024)
Publisher : Electrical Engineering, Universitas Mercu Buana

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.22441/jte.2024.v15i1.003

Abstract

Microgrids are a technology that is developing quite rapidly and is attracting world attention in facing the energy and pollution crisis. There are three types of microgrid structures: AC, DC, and AC-DC hybrid microgrid. Because it consists of an AC bus and a DC bus, AC-DC hybrid microgrids can connect more types of Distributed Generation (DG) and have smaller converter losses, making it more economical and reliable than other types of microgrids. Due to the use of nonlinear devices, harmonic distortion in microgrids is a problem that needs to be solved. In this research, the AC-DC hybrid microgrid system is simulated using ETAP software. Then the characteristics of the distribution of harmonics in the system obtained from harmonic load flow simulations are also analyzed. Following the installation of the passive filter, Bus 1 and Bus 2 now suitable to the IEEE Std standards 519-1992 for harmonic values. After the application of the filter, Bus 1 refer a THD of 1.32%, while Bus 2 indicate a THD of 0.84%. In addition, the Individual Harmonic Distortion (IHD) for Bus 1 has dropped below 3% at the 5th harmonic and below 1.5% at the 13th harmonic. Besides that, Bus 2 IHD has decreased to less than 3% at the 11th harmonic and less than 1.5% at the 13th harmonic.
Pendampingan Pembentukan Kader Hulu Sampah Di Desa Minggirsari Kabupaten Blitar Masrunik, Endah; Andriawan, Aris Heri; Jatmiko, Dheny; Khomariah, Nuril Esti
Jurnal Masyarakat Indonesia (Jumas) Vol. 4 No. 01 (2025): Jurnal Masyarakat Indonesia (Jumas)
Publisher : Cattleya Darmaya Fortuna

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.54209/jumas.v4i01.171

Abstract

The aim of implementing this community service is to form upstream waste cadres in Minggirsari Village, so that existing waste can be managed well and the community has motivation in managing their household waste. The implementation method for this activity is carried out by holding socialization about the upstream waste cadres of Minggirsari Village, which is then provided with ongoing assistance so that the upstream waste can work according to its function and is able to increase the number of waste bank members. The result of this activity is the formation of upstream waste cadres in Minggirsari, household waste is well managed, this is proven by the increasing number of waste bank members and the increasingly active existing waste banks. Apart from that, with the assistance provided by the upstream waste cadres, they are increasingly active in holding socialization or education on the importance of sorting waste and realizing several blessing sacks of waste in
Analysis of Leakage Current Calculation Through Thermal Failure Voltage on 150/20 kV Transformers in GIS Simpang, Surabaya Widagdo, Reza Sarwo; Andriawan, Aris Heri; Suri Tauladan, Imam; Ivan Maulana, Ade
Jurnal ELEMENTER (Elektro dan Mesin Terapan) Vol 10 No 2 (2024): Jurnal Elektro dan Mesin Terapan (ELEMENTER)
Publisher : Politeknik Caltex Riau

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.35143/elementer.v10i2.6366

Abstract

In the current test, leaks really need to be carried out at GIS Simpang. This test was carried out by strengthening the 20 kV incoming cable in the GIS Simpang 150/20 kV transformer bay. The impact of measuring this leakage current is to reduce the occurrence of leakage currents so that they are not too severe because this can determine how much the leakage current increases in the incoming cable. The trend test results were measured to determine the comparison between the leakage current in January and the leakage current measurement process at GIS Simpang. Based on the results of leakage current testing on transformer 1 and transformer 2 incoming 20 kV cables from several phases, it shows that the results of the leakage current trend in the cables have not increased significantly. However, from the calculation results listed, it can be seen from the comparison table that the results have increased during the calculation and have slight differences compared to the leakage current measurement results themselves. This is because from the calculation results, the cable temperature detection experienced a slight increase in the cable temperature as measured by thermovision to determine the thermal failure voltage. However, the cable is still suitable for operation because the temperature of the cable itself has a standard that does not exceed 150C for several measured cable phases.
Technical Support for Maintaining Solar Power Plants in Plantation Areas, Sajen Village, Mojokerto Widagdo, Reza Sarwo; Ardianik, Ardianik; Imam Suri Tauladan; Slamet, Puji; Andriawan, Aris Heri; Hariadi, Balok
BERNAS: Jurnal Pengabdian Kepada Masyarakat Vol. 6 No. 3 (2025)
Publisher : Universitas Majalengka

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.31949/jb.v6i3.13233

Abstract

Sajen Village is predominantly an agricultural and livestock-based community. However, the lack of sufficient electricity poses a significant challenge to the development of these sectors. Solar Power Generation Technology offers a sustainable solution due to the village’s potential for utilizing solar energy. To ensure the successful implementation of solar power plant, it is essential to provide the local community with adequate knowledge and skills in its operation, maintenance, and care. This community service program aims to introduce solar power plant to the residents of Sajen Village while equipping them with the necessary technical expertise. The program consists of several key activities: training on solar power plant operation and maintenance, an introduction to the principles of solar power plant design and installation, and evaluation sessions to assess the community's understanding. These activities are designed to empower participants to independently operate and maintain solar power plant systems. The final stage involves evaluating the program’s effectiveness by measuring the participants’ comprehension of solar power plant concepts, operations, and maintenance techniques. This initiative is expected to enhance the sustainability of Sajen Village's agricultural and livestock sectors by addressing the electricity shortage through renewable energy solutions. It also promotes community independence in managing solar power systems for long-term benefits
Penyuluhan Tentang Penggunaan Sumber Alternatif Solar Panel untuk Penerangan di Desa Jebreng Wonosari Ridho’i, Ahmad; Santoso, Santoso; Shidiq, Nujhad; Andriawan, Aris Heri
Jurnal Pengabdian Masyarakat Bhinneka Vol. 3 No. 4 (2025): Bulan Juli
Publisher : Bhinneka Publishing

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.58266/jpmb.v3i4.149

Abstract

Pengabdian masyarakat ini bertujuan untuk meningkatkan kesadaran dan pengetahuan masyarakat Desa Jebreng, Wonosari, mengenai pemanfaatan energi surya melalui penggunaan panel surya sebagai sumber penerangan alternatif. Kegiatan penyuluhan yang dilakukan mencakup materi tentang prinsip kerja panel surya, manfaat penggunaan energi surya, serta cara pemasangan dan perawatan panel surya. Selain penyuluhan, juga dilakukan demonstrasi langsung pemasangan panel surya di beberapa titik strategis di desa. Hasil evaluasi menunjukkan bahwa kegiatan penyuluhan ini berhasil meningkatkan pemahaman masyarakat tentang pentingnya energi terbarukan dan minat mereka untuk beralih ke penggunaan panel surya. 
Estimated Life Loss of a 3-Phase Induction Motor Based on Insulation Resistance Test at PT. Delta Jaya Mas Widagdo, Reza Sarwo; Slamet, Puji; Andriawan, Aris Heri
Jurnal Teknologi Elektro Vol 15, No 3 (2024)
Publisher : Electrical Engineering, Universitas Mercu Buana

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.22441/jte.2024.v15i3.001

Abstract

At the company PT. Delta Jaya Mas induction motors are very necessary to run machines in the production process. An induction motor consists of a rotor and stator with insulation resistance. Insulation Resistance (IR) is a measure of the ability of the insulation in the winding to withstand current. Insulation resistance testing is needed to determine the condition of the insulation which is influenced by humidity, environmental temperature and operating time. This test procedure is regulated in the IEEE Std 43-2000 standard. The use of an appropriate insulation tester and routine testing is important to maintain the insulation resistance value and prevent accidents and damage to 3-phase induction motors. Testing is carried out when the motor is turned off to avoid component damage. Polarization index data is taken by testing the insulation resistance for 1 to 10 minutes. The test was carried out on the insulation resistance of a three-phase induction motor with a power of 75 kW which showed a value of 515 MΩ to 602 MΩ when it was in a damaged condition with one phase having a value of 0 MΩ indicating a short or short circuit condition. After repair the motor has an insulation resistance of 2000 MΩ. After operating for 3 months the decrease in resistance that occurred per month was 11.6 MΩ and the polarization index test was 3.5 MΩ. An insulation resistance of 2000 MΩ can be expected to last for 14 years if degradation occurs consistently.
Pengembangan Filter Adaptif Berbasis Least Mean Square untuk Pengurangan Noise pada Sinyal Elektrokardiogram Setyadjit, Kukuh; Santoso, Santoso; Hariz, Muhammad Amsyaril; Muhammad, Reyhan Ihsan; Slamet, Puji; Andriawan, Aris Heri; Hartayu, Ratna
Prosiding Seminar Nasional Teknik Elektro, Sistem Informasi, dan Teknik Informatika (SNESTIK) 2025: SNESTIK V
Publisher : Institut Teknologi Adhi Tama Surabaya

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.31284/p.snestik.2025.7539

Abstract

Electrocardiogram (ECG) signals are often affected by various types of noise, such as electromagnetic interference, patient body movement, and disturbances from other medical devices, which can degrade the signal quality and hinder accurate detection of heart disorders. This study aims to compare the performance of various filters in reducing noise in ECG signals, focusing on the Highpass-Lowpass filter and the Least Mean Square (LMS) adaptive filter. The testing was conducted using metrics such as Mean Squared Error (MSE), Signal-to-Noise Ratio (SNR), average amplitude, total error, and computation time. The experimental results show that the LMS filter provides the best results, with an MSE value of 0.0045, SNR of 21.5 dB, and total error of 4.78, indicating its ability to produce a cleaner signal compared to the Highpass-Lowpass filter. The LMS filter also demonstrates good computational efficiency, with a time of 0.102 seconds. With its ability to dynamically adjust filter parameters, the LMS filter proves effective in reducing both low and high-frequency noise in ECG signals. This study shows that the LMS filter can be effectively applied to process ECG signals contaminated by noise and contributes to improving the accuracy of heart disorder diagnosis
Penggunaan Citra sebagai Penyuluhan Masyarakat yang Berada di Rawan Terjadi Bencana Tanah Longsor Ridho’i, Ahmad; Sidiq, Nujhad; Sarya, Gede; Andriawan, Aris Heri
Jurnal Pengabdian Masyarakat Bhinneka Vol. 4 No. 1 (2025): Bulan September
Publisher : Bhinneka Publishing

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.58266/jpmb.v4i1.333

Abstract

Landslides are a serious threat in various regions of Indonesia, causing material losses and casualties. Communities residing in landslide-prone areas often have a low level of understanding and awareness regarding disaster risks and their mitigation. Therefore, this community service aims to implement and evaluate the effectiveness of using imagery as an innovative and easily understandable outreach medium for communities in landslide-prone areas. Conventional, verbally-oriented outreach methods are often less effective in conveying technical information to the general public, especially given varying literacy levels. This community service adopts a descriptive qualitative approach with case studies in several villages in Ponorogo, East Java, identified as landslide-prone areas. Data was collected through participant observation, in-depth interviews with community representatives and village officials, and Focus Group Discussions (FGDs). The imagery used in this service includes aerial photographs, disaster-prone maps, and visual illustrations of landslide mechanisms, early warning signs, and relevant evacuation and mitigation steps. These images were then integrated into interactive outreach materials and presented in engaging formats, such as infographics, posters, and visual presentations.
Peningkatan Kualitas Sinyal Elektrokardiogram dengan Filter Adaptif Recursive Least Squares Santoso, Santoso; Hartayu, Ratna; Slamet, Puji; Andriawan, Aris Heri; Setyadjit, Kukuh; Cahyono, Mochammad Irfan; Jabaruddin, Abdul
INTEGER: Journal of Information Technology Vol 10, No 2 (2025): September
Publisher : Fakultas Teknologi Informasi Institut Teknologi Adhi Tama Surabaya

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.31284/j.integer.0.v10i2.7775

Abstract

This paper presents a comparative analysis of two adaptive filtering algorithms, namely Least Mean Square (LMS) and Recursive Least Square (RLS), for denoising electrocardiogram (EKG) signals contaminated with Gaussian noise. A five-second EKG signal was extracted from a PhysioNet database and artificially corrupted by additive white Gaussian noise. The noisy signal was then processed using both LMS and RLS filters, where parameter tuning was applied to each algorithm to optimize performance. The evaluation metrics used in this study include Mean Squared Error (MSE) and Signal-to-Noise Ratio (SNR). Experimental results demonstrate that the LMS filter achieved its best performance at a learning rate (μ) of 0.01, resulting in an MSE of 0.1218 and an SNR of 4.18 dB. In contrast, the RLS filter provided superior results with a forgetting factor (λ) of 0.99, achieving an MSE of 0.1179 and an SNR of 4.32 dB. These findings indicate that while RLS outperforms LMS in terms of signal recovery accuracy, LMS remains advantageous in computational simplicity and is more suitable for real-time applications. The comparative analysis suggests that the choice between LMS and RLS should consider the trade-off between denoising performance and computational efficiency, especially in portable or embedded biomedical devices.