Claim Missing Document
Check
Articles

Found 7 Documents
Search

Pengaruh Masukan Dan Fungsi Aktivasi Terhadap Kecepatan Pelatihan Jaringan Syaraf Tiruan (JST) Modular Sebagai Klasifikasi Dan Estimasi Lokasi Gangguan Pada Saluran Distribusi Bawah Tanah PT. Pertamina RU II Dumai Boy Ihsan; Dian Yayan Sukma
Jurnal Online Mahasiswa (JOM) Bidang Teknik dan Sains Vol 4, No 1 (2017): Wisuda Februari Tahun 2017
Publisher : Jurnal Online Mahasiswa (JOM) Bidang Teknik dan Sains

Show Abstract | Download Original | Original Source | Check in Google Scholar

Abstract

This paper describes a method of modular artificial neural network (ANN) for identifying and locating short circuit faults in underground power distribution line at PT. Pertamina RU II Dumai. The underground power distribution line is modeled using ATP-EMTP software. ANN-based fault classifier made from ANN-based fault detection in different phases and ground which work in parallel. ANN- based fault locator made form ANN which is estimated locations of fault occurs for each different types of fault. The ANN-based fault classifier of fault was performed variety of the given input and The ANN-based fault locator was performed variety of the activation function type which is deployed in different layer. The study result shows 4 different sampling of voltage value as ANN-based fault detection input in different phase fault. In the another result shows 4 different sampling of zero sequence current value as ANN-based fault detection input in ground fault. The last result shows the activation function of ANN-based fault locator is sigmoid bipolar – sigmoid biner – linear in the different ANN-based fault locator. All the previous result was aggregated to enhance the training phase in order to speed up in achieving MSE target of 1E-5.Keywords: modular artificial neural network (ANN), fault classifier, fault locator, short circuit faults , underground power distribution line
Pengaruh Strategi Pengisian Daya Terhadap Kenaikan Beban Puncak Akibat Penetrasi Kendaraan Listrik Boy Ihsan; Deny Hamdani; Nanang Hariyanto
Jurnal Nasional Teknik Elektro dan Teknologi Informasi Vol 9 No 3: Agustus 2020
Publisher : Departemen Teknik Elektro dan Teknologi Informasi, Fakultas Teknik, Universitas Gadjah Mada

Show Abstract | Download Original | Original Source | Check in Google Scholar | Full PDF (1223.334 KB) | DOI: 10.22146/.v9i3.363

Abstract

To overcome the problem of energy crisis and global warming, many countries in the world are pushing growth in the use of electric vehicles. In the future, the use of electric vehicles in large numbers will also occur in Indonesia and charging electric vehicles will become a new load on the electricity system. One of the effects of electric vehicle penetration is an increase in the system's peak load. Therefore, this study examines how the increase in daily load due to penetration of electric vehicles and how the strategy of electric vehicles charging to reduce the increase in load on one of the electricity systems in Indonesia, namely the Jawa-Bali system. The calculation results show that the Jawa-Bali electrical system is only able to accommodate electric vehicle penetration by 20% if the problem of losses, instability, and line loading are ignored. In the case of 10% penetration of electric vehicles, the peak load of the Jawa-Bali system increased by 5,857 MW. However, by scheduling electric vehicle charging, the increase in peak load can be reduced by 3,232 MW and by using the V2G scheme, the energy supplied by the system generator can be reduced by 20,003 MWh.
Pelatihan Electrical Transient Analysis Program Software (ETAP) Mendukung Program Teaching Factory (TEFA) pada Tingkat Sekolah Menengah Kejuruan (SMK) Tauladan, Imam Suri; Syamsir, Hendri Novia; Sahar, Muzni; Ihsan, Boy
BATOBO: Jurnal Pengabdian Kepada Masyarakat Vol 2 No 2: BATOBO: Desember 2024
Publisher : Jurusan Teknik Elektro

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.31258/batobo.2.2.111-118

Abstract

Menghadapi permasalahan tuntutan industri yang semakin tinggi terhadap lulusan vokasi serta sulitnya mengimplementasikan metode pembelajaran teaching factory pada tingkat pendidikan kejuruan, diperlukan transfer pengetahuan dari perguruan tinggi untuk masyarakat khususnya Guru dan Siswa/i Sekolah Menengah Kejuruan Negeri (SMKN) 2 Pekanbaru. Saat ini tuntutan industri mengisyaratkan bahwa lulusan vokasi terampil dalam penggunaan software yang berhubungan dengan elektro arus kuat salah satunya software ETAP. Selain itu Guru Jurusan Teknik Tenaga Listrik dan Teknik Instalasi Listrik SMKN 2 Pekanbaru, belum mendapatkan pendampingan penerapan teknologi dalam pelatihan ETAP software. Sehingga perlunya kegiatan transfer ilmu teknologi pelatihan ETAP untuk mendukung program teaching factory (TEFA). Metode pelaksanaan pelatihan yang digunakan berbasis metode workshop. Penggunaan metode workshop bertujuan untuk kegiatan yang interaktif untuk meningkatkan pemahaman dan mengembangkan keterampilan dalam materi yang disajikan. Adapun materi yang dibahas pada pelatihan ini adalah analisa aliran daya pada sistem kelistrikan radial yang bertujuan untuk memperbaiki level tegangan pada bus dan menganalisis aliran daya pada setiap bus. Dari hasil kegiatan workshop menunjukkan Guru dan Siswa/i dapat melakukan simulasi analisa aliran daya dengan menggunakan software ETAP. Selain itu, peserta mampu melakukan mitigasi terhadap permasalahan penurunan profil level tegangan pada bus sistem kelistrikan.
Peningkatan Umur Baterai pada PLTS Off-grid menggunakan Penyimpanan Energi Hibrida Berbasis Superkapasitor-Baterai Ihsan, Boy; Sahidin, Dwi; Rachmildha, Tri Desmana; Hamdani, Deny
E-JOINT (Electronica and Electrical Journal Of Innovation Technology) Vol. 5 No. 2 (2024): E-JOINT, Desember 2024
Publisher : Politeknik Negeri Cilacap

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.35970/e-joint.v5i2.2560

Abstract

Perubahan iklim akibat pemanasan global menuntut penggunaan teknologi pembangkit listrik yang ramah lingkungan. Pembangkit Listrik Tenaga Surya (PLTS) merupakan salah satu pembangkit yang ramah lingkungan. Namun, pembangkit ini bersifat intermiten sehingga jika dioperasikan secara off-grid akan memerlukan perangkat penyimpanan energi. Paper ini merancang suatu sistem PV off-grid pada daerah 3T (tertinggal, terdepan, dan terluar) di Indonesia dengan menggunakan sistem penyimpan energi hibrida, yaitu baterai dan superkapasitor. Fluktuasi energi jangka pendek diutamakan ditangani oleh superkapasitor, sedangkan energi jangka panjang yang lebih stabil disuplai oleh baterai. Pendekatan ini bertujuan mengurangi stres dan siklus charge-discharge baterai, sehingga memperlambat degradasi baterai. Performa dari sistem ini diuji dengan melakukan pemodelan dan simulasi aliran energi pada MATLAB. Berdasarkan hasil simulasi, dilakukan prediksi umur baterai dengan menggunakan algoritma rain flow counting dan perhitungan Levelized Cost of Energy (LCOE) dari sistem pembangkit. Hasil penelitian menunjukkan bahwa penambahan superkapasitor pada sistem penyimpanan energi dapat menstabilkan transien daya dan mengurangi siklus charge-discharge baterai, sehingga memperpanjang umur baterai . Selain itu, LCOE pada sistem dengan superkapasitor lebih rendah daripada sistem tanpa superkapasitor.
TRANSFORMER HEALTH CONDITION ANALYSIS BASED ON HEALTH INDEX AND FAILURE METHOD Iswadi Hasyim Rosma; Boy Ihsan; Jikro Pikri
TESLA: Jurnal Teknik Elektro Vol 27 No 2 (2025): TESLA : Jurnal Teknik Elektro
Publisher : Universitas Tarumanagara

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.24912/tesla.v27i2.35671

Abstract

Transformers are one of the important assets whose health conditions need to be monitored to maintain operating reliability and prevent failures. Regular monitoring and testing can be done on transformer oil and insulating paper (furan). This article aims to evaluate the health index, estimate the remaining life and detect potential transformer failures. The test data used was obtained from two transformers at a biodiesel producing company in Indonesia, such as Dissolved Gas Analysis, Breakdown Voltage, Water Content, Acid, Interfacial Tension and 2 Fal (furan) tests. The method used in the diagnosis of transformer health conditions is the transformer health index method and analysis of potential failures based on the evaluation of Total Dissolved Combustible Gas, Roger's Ratio and Duval's Triangle. The results show that both transformers are in a healthy condition with a health index of 72% and 89%, which fall into the “Good” and “Very Good” categories, and the estimated operational life is more than 10 years and 15 years, respectively. However, the failure analysis results indicated an overheating failure with a temperature exceeding 700 ºC. Although the overall transformer condition is still good, preventive maintenance measures are still recommended to avoid more serious damage in the future Abstrak Transformator merupakan salah satu aset penting yang kondisi kesehatannya perlu dipantau untuk menjaga keandalan operasi dan mencegah kegagalan. Pemantauan dan pengujian secara berkala dapat dilakukan terhadap minyak transfomator dan isolasi kertas (furan). Artikel ini bertujuan untuk mengevaluasi indeks kesehatan, estimasi sisa umur dan mendeteksi potensi kegagalan transformator. Data pengujian yang digunakan diperoleh dari dua transformator di sebuah perusahaan penghasil biodiesel di Indonesia yaitu data hasil pengujian Dissolved Gas Analysis, Breakdown Voltage, Water Content, Acid, Interfacial Tension serta 2 Fal (furan). Metode yang digunakan dalam diagnosis kondisi kesehatan transformator adalah metode indeks kesehatan transformator serta analisis potensi kegagalan berdasarkan evaluasi Total Dissolved Combustible Gas, Roger’s Ratio dan Duval’s Triangle. Hasil penelitian menunjukkan bahwa kedua transformator berada dalam kondisi sehat dengan indeks kesehatan 72% dan 89%, yang termasuk kategori “Baik” dan “Sangat Baik”, serta estimasi umur operasional masing-masing lebih dari 10 tahun dan 15 tahun. Namun demikian, hasil analisis kegagalan mengindikasikan adanya kegagalan overheating dengan suhu melebihi 700 ºC. Meskipun kondisi keseluruhan transformator masih baik, tindakan pemeliharaan preventif tetap direkomendasikan untuk menghindari kerusakan yang lebih serius dimasa mendatang.
Peningkatan Umur Baterai pada PLTS Off-grid menggunakan Penyimpanan Energi Hibrida Berbasis Superkapasitor-Baterai Ihsan, Boy; Sahidin, Dwi; Rachmildha, Tri Desmana; Hamdani, Deny
E-JOINT (Electronica and Electrical Journal Of Innovation Technology) Vol 5 No 2 (2024): E-JOINT, Desember 2024
Publisher : Politeknik Negeri Cilacap

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.35970/e-joint.v5i2.2560

Abstract

Perubahan iklim akibat pemanasan global menuntut penggunaan teknologi pembangkit listrik yang ramah lingkungan. Pembangkit Listrik Tenaga Surya (PLTS) merupakan salah satu pembangkit yang ramah lingkungan. Namun, pembangkit ini bersifat intermiten sehingga jika dioperasikan secara off-grid akan memerlukan perangkat penyimpanan energi. Paper ini merancang suatu sistem PV off-grid pada daerah 3T (tertinggal, terdepan, dan terluar) di Indonesia dengan menggunakan sistem penyimpan energi hibrida, yaitu baterai dan superkapasitor. Fluktuasi energi jangka pendek diutamakan ditangani oleh superkapasitor, sedangkan energi jangka panjang yang lebih stabil disuplai oleh baterai. Pendekatan ini bertujuan mengurangi stres dan siklus charge-discharge baterai, sehingga memperlambat degradasi baterai. Performa dari sistem ini diuji dengan melakukan pemodelan dan simulasi aliran energi pada MATLAB. Berdasarkan hasil simulasi, dilakukan prediksi umur baterai dengan menggunakan algoritma rain flow counting dan perhitungan Levelized Cost of Energy (LCOE) dari sistem pembangkit. Hasil penelitian menunjukkan bahwa penambahan superkapasitor pada sistem penyimpanan energi dapat menstabilkan transien daya dan mengurangi siklus charge-discharge baterai, sehingga memperpanjang umur baterai . Selain itu, LCOE pada sistem dengan superkapasitor lebih rendah daripada sistem tanpa superkapasitor.
Comparison of Transient Mitigation through Synchronous Closing and Capacitor Switching in 150 kV Networks Firdaus; Apriyal, Derry; Azhari Zakri, Azriyenni; Ihsan, Boy; Sultana, Beenish
International Journal of Electrical, Energy and Power System Engineering Vol. 8 No. 3 (2025): The International Journal of Electrical, Energy and Power System Engineering (I
Publisher : Electrical Engineering Department, Faculty of Engineering, Universitas Riau

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.31258/ijeepse.8.3.323-336

Abstract

This study addresses the challenge of transient voltage and current surges caused by capacitor bank switching in high-voltage transmission systems, which can compromise equipment integrity and system stability. The research focuses on optimizing the mitigation of these transients in a 150 kV transmission line using the synchronous closing breaker method. Simulations were conducted in MATLAB/Simulink using actual parameters provided by the power utility. To verify the accuracy of the Simulink model and its results, validation was performed in DIgSILENT PowerFactory by comparing steady-state voltage responses following capacitor switching. With the model validated, three operating scenarios were examined: no capacitor bank, conventional capacitor bank switching, and with the implementation of synchronous closing breakers. The synchronous closing method significantly reduced transient voltage and current magnitudes compared to conventional switching. These outcomes confirm the effectiveness of the synchronous closing breaker in minimizing transient disturbances. The findings contribute to the development of improved transient mitigation strategies and offer a practical reference for large-scale capacitor bank deployment, particularly in smart grid applications. This method provides a cost-effective and scalable approach for improving power quality in modern high-voltage transmission networks.