Strategy to reduce transient current of inverter-side on an average value model high voltage direct current using adaptive neuro-fuzzy inference system controller Ginarsa, I Made; Ari Nrartha, I Made; Budi Muljono, Agung; Sultan, Sultan; Nababan, Sabar
International Journal of Electrical and Computer Engineering (IJECE) Vol 12, No 5: October 2022
Publisher : Institute of Advanced Engineering and Science

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.11591/ijece.v12i5.pp4790-4800

Abstract

Growing-up of high voltage direct current (HVDC) penetration into modern power systems (PS) makes difficulty on the PS operation. The HVDC produces high and slow transient current (TC) at start-time, especially for higher up-ramp rate (Urr>20 pu/s). Its condition makes the HVDC cannot be linked and synchronized into the PS rapidly. A strategy to reduce the TC is proposed by an adaptive network based fuzzy inference system (ANFIS) control on inverter HVDC-link to cope up this problem. The ANFIS control is tuned with the help of conventional control in various train-data by using offline mode. Response of ANFIS scheme is improved by suppressing TC at the values of 3.75% for the both phases (A and C), and 3.95% for phase B, for the Urr=30 pu/s. While the conventional control achieved at 9.1% for the both phases (A and B), and 9.2% for the phase C. The ANFIS control gives shorter settling time (0.553 s) than the conventional control (0.584 s) for all phases. The proposed control is more effective than the conventional control at all the scenario.