Analysis Grounding System as Building Equipment Security Udayana University Denpasar I G. N. Janardana; W. Arta Wijaya; Cok Gede Indra Partha; N. Budiastra
Journal of Electrical, Electronics and Informatics Vol 1 No 2 (2017): JEEI (September 2017)
Publisher : Institute for Research and Community Services Udayana University

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.24843/JEEI.2017.v01.i02.p03

Abstract

Grounding system is one of the components in building equipment security. To fulfill the operational continuity of electronic equipment in Faculty of Engineering, Udayana University, Denpasar, a grounding system with a ground resistance of ? 3 ohms is required to be installed. The aim of this study is to find out the characteristics of grounding system to secure the equipment in the building around the research location, with ground resistance of ? 3 ohms and it is expected to be beneficial to use as a reference in grounding system installation as well as. According to the measurement results at the research location, it is found that the soil resistance value is equal to 0.23 ohms, where the soil resistivity (?) is 28.89 Ohm-meters. There are some results analysis obtained in ground resistance value of ? 3 Ohm. Those are 1) grounding system type 1 rod where minimal depth installation of the electrode is 14 meters with ground resistance value of 2.6751 ohms; 2) grounding system type two rod with s < L, it is obtained that each depth is 8 meters with distance of 2 meters between electrodes, where the ground resistance value is 2.4940 ohms. In the installation of two electrodes with s > L, it is gained that the depth of each electrode is 6 meters where the distance between the electrodes is 8 meters and the ground resistance value is 2.8718 ohms. By applying the plates type grounding system with 3 meters in length, 1 meter in width, and 2 meters in installation depth is gained 2.8431 ohms ground resistance value. Furthermore, by applying grid type grounding system with 2 meters in length h = 2,5 meters in depth, A = 4 meters in width and the total length of the electrode diameter 1 cm is 504 meters, it is obtained 2.0978 ohms ground resistance value.
Study of Electrical Systems in Engineering Faculty Udayana University Bukit Jimbaran I G. N. Janardana; W. Arta Wijaya
Journal of Electrical, Electronics and Informatics Vol 3 No 2 (2019): JEEI (August 2019)
Publisher : Institute for Research and Community Services Udayana University

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.24843/JEEI.2019.v03.i02.p02

Abstract

Electrical systems that serve the Dean of electricity load, the electricity load of the Departement of Architecture, Departement of Mechanical Engineering, Departement of Electrical Engineering, Departement of Information Technology, external lighting facilities supplied by transformers with a capacity of 200 KVA. Lately the quality electrical system has begun to decline with frequent interruptions such as the breakdown of electricity to the load, unbalanced load, THD current exceeds the standard, the fuse on the incoming to the parent panel and the fuse on the main panel is often burned, the grounding system resistance value exceeds the standard equipment value, cable temperature exceeds the standard, even voltage rises to 500 volts. The purpose of this study is to determine the causes of disruption of electricity, and produce a new master installation design to improve the system. Based on the results of the analysis, it was found that the importance of channel separation between loads to the Dean building with the Departement of Architecture building with cable capacity for the Dean building of NYY 4 x 95 mm2 and the safety of the NFb 200 Ampere mains. For cables to the building load, the Departement of Architecture installed a new main cable with NYY 4 x 50 mm2 cable size and NFb 150A main safety. It is necessary to replace the main NFb safety at the MDP parent panel which supplies the load to the Departement of Mechanical Engineering building from 160 Ampere to 200 Ampere. The entire phase in each panel does not meet the IEEE 519 - 2014 standard, so it is very important to install a filter. Ground resistance values ??on all panels vary above the standard with a value of 12 to 62 ohms. So it needs to be made a new grounding. When using a plate grounding system, the number of plates that need to be planted is 25 sheets with a size of 2m x 1 m with a planting depth of 2 m. Whereas when using a grid type earth system, a grid with a size of 3 meters x 3 meters is needed with a total grid length of 2976 meters and a depth of 3 meters.
Effect Of Value Of Resistance Announcement To Thd In Electrical System Faculty Of Engineering University Udayana Denpasar I. G. N. Janardana; I W Arta Wijaya; I. N. Karnata Mataram
Journal of Electrical, Electronics and Informatics Vol 2 No 1 (2018): JEEI (February 2018)
Publisher : Institute for Research and Community Services Udayana University

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.24843/JEEI.2018.v02.i01.p05

Abstract

AC (Air Conditioner), TV, lamp, LCD and others are categorized as nonlinear load generating harmonics. The high content of harmonics has a negative impact on the quality of electrical power. The result of measurement of THD (Total Harmonic Distortion) current at 9 ohm ground resistance value at phase R = 9,8%, phase S = 11,0%, phase T = 7,5% exceed from standard value IEEE 519 Year 2014 equal to ? 5 , 0%, THD measurement of phase voltage R = 1.4%, phase S = 1.2%, phase T = 1.3%, meet the maximum THDv standard of ? 5%. To overcome this problem, it was observed the effect of the value of ground resistance to THDi and THDv on the electrical system of the College of Engineering Faculty of Denpasar. This method of analysis with ETAP software simulation. With grounding system ? 3 ohm only effect on current THD only with decreasing value of THDi become: phasa R = 4,2%, phase S = 5% and phase T = 4,3%, meaning with grounding system ? 3 ohm THD current fulfill IEEE 519 - 2014 standard <5%. while THD voltage has no effect (THD value of fixed voltage). Several studies have suggested that THD repair can be done by filter installation. However in this study the installation of grounding system ? 3 ohms can reduce the value of current THD.
Master Installation Design And Transformer Need Analysis in Faculty of Engineering Udayana University Denpasar IGN Janardana; Wayan Arta Wijaya
Journal of Electrical, Electronics and Informatics Vol 4 No 1 (2020): JEEI (February 2020)
Publisher : Institute for Research and Community Services Udayana University

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.24843/JEEI.2020.v04.i01.p05

Abstract

Faculty of Engineering, Udayana University, PB. Sudirman Denpasar has 5 building units (buildings A, B, C, D, AF). Currently the AF building is undergoing renovation and is planned to be on 4 floors. The entire building will be equipped with the installation of 2 elevator units. The construction of the two new buildings and the installation of the 2 elevator units caused new problems of electricity shortages, changes in safety settings, unbalanced loads, and changes in the size of the main cable and the needs of the transformer and its capacity. The AF building and building A are supplied from sources on the transformer which are joined with other faculties, while Buildings B, C, D and E are fed by one transformer No. 124303818 with a capacity of 160 kVA. The plan to build an Alumni Building does not yet have electricity. Based on the analysis of the design, the total amount of power needed in all buildings in the Sudirman Denpasar Faculty of Engineering is the result of the AF Building planning = 134,280 watts, the Alumni Building planning results (building area and building functions are considered equal = 134,280 watts), so the total needs power to the two buildings = 271 560 Watt with a load deviation of 65%, then 0.65 x 271 560 W = 176 514 Watt. Then the total power requirement of the entire building is 259,340 watts. The measurement result of Cos ? 0.92, then P (kVA) = 281,891,3043 Ampere = 281,8913 kVA. So that the transformer needs that must be prepared by the Faculty of Engineering to meet the power requirements at the Faculty of Engineering, Udayana University Denpasar with 80% transformer efficiency is a 350 kVA transformer with a placement position around the Faculty of Engineering area
Graphic Monitoring on Test of Rocket Launch Payload I N. Budiastra; C. G. I. Partha; I G. N. Janardana; I W. A. Wijaya
Journal of Electrical, Electronics and Informatics Vol 1 No 2 (2017): JEEI (September 2017)
Publisher : Institute for Research and Community Services Udayana University

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.24843/JEEI.2017.v01.i02.p01

Abstract

Aviation technology and space is one of the leading technology for developed countries, especially in the form of rocket technology and charge. The countries that are capable of mastering these technologies will be respected by countries all over the world. Indonesia as the island nation with large and extensive maritime should have independence in the mastery of the technology of the rocket and payload. Therefore, continuous efforts are required to achieve independence, including through enhancing the sense of love of aviation technology and space technology, particularly at early stages the rocket and payload. Graphic Monitoring Test Rocket Launch Payload Attitude is the attitude of remote monitoring launch vehicle through the computer screen (display) continuously (real-time) data obtained from sensors-sensors that are mounted on the rocket's payload. 3D point (x, y, z) must be expressed as a graph visualization perspective drawings of rockets with the appropriate direction. The radar conducted computer GS (Ground Segment) or Ground Control Station (GCS. The result of the attitude of the Rocket Test launch Payloads have been able to communicate with the 3D data sending (x, y, and z) in real-time to the Ground segment. Wireless communication uses radio telemetry frequency 433 MHz, power of 100 mW, the distance range obtained in this study a maximum of 500 Meters in the air, without a hitch.
Coral Rock Thickness Grounding System Switchyard Substation In Clay IGN Janardana; I Wayan Arta Wijaya
Journal of Electrical, Electronics and Informatics Vol 7 No 1 (2023): JEEI (July 2023)
Publisher : Institute for Research and Community Services Udayana University

Show Abstract | Download Original | Original Source | Check in Google Scholar

Abstract

The grounding of the equipment at the substation switchyard location is given a layer of coral about 10 cm above the ground surface to reduce the tension difference on the ground surface and increase the resistance of the human feet around it. The purpose of this study was to determine the thickness of the coral in the grounding system of switchyard equipment in clay. This research analysis method calculates the results of the coral thickness value to achieve the step voltage and touch voltage values ??according to the IEEE Std 80-2013 standard so that it can provide safety for the equipment and people around it. The results of this study are that the thickness of the coral 0.15 meters produces a touch voltage value = 150.3675 volts (dry conditions) and 148.63 volts (wet conditions) and the step voltage is the smallest and best with a value = 206.83 volts ( dry conditions) and 163.98 volts (wet conditions when compared to the thickness of the coral 0.08 meters to 0.14 meters, so it is concluded that the thickness of the coral is best to be installed at the substation on clay of 0.15 meters is good when the soil and coral are wet or dry, so that it has an impact on the function of the grounding system to function properly and safely for equipment and humans. Keywords— Coral, Earthing, Clay.
Co-Authors A A G M Pemayun A I Weking A. I. Weking A.A Ngurah Amrita AA. M Pemayun Achmad Noerkhaerin Putra Aggry Saputra Anandita Praja Dwitama Ananta Wijaya Ariany Frederika Biantoro, Kharis C G I Partha C G I Partha Dewa Agung Krishna Arimbawa P dwi ardiada Fachri Zamzami Ferry Ardiansyah Fransiskus Xaverius Saav Agus I B Gede Manuaba I G. P. A. Wartama I G.B. Satcitananda P I G.N Nanda Ramdipa Amerta I Gede Agus Handi Saputra I Gede Dyana Arjana I Gede Feryanda Fransiska I Gede Putu Aditya Kresna Artha K I Gst Agung Putu Raka Agung I Gusti Putu Andhita Mahayana I Kadek Agus Wahyu Raharja I Kadek Dwi Artika Putra I Komang Suarjana I M Dwijaksana I M Suartika I Made Darmayusa I Made Dhanan Pradipta I Made Mudiarta I Made Suartika I Made Surya Ganesputra I Made Suwartama Wijaya I Nyoman Angga Prabawa I Nyoman Apriana Arta Putra I Nyoman Arnawan I Nyoman Budiastra I Nyoman Budiastra I Nyoman Julyantara I Nyoman Mudana I Putu Andrean Wiranata I Putu Arich Arthawan I Putu Bayu Suka Yasa I Putu Nanda Nugraha Utama I Putu Nova Suciawan I W A Wijaya I W Arta Wijaya I W Rinas I W. A. Premei Artha I W. A. Wijaya I W. A. Wijaya I W. Rinas I W.A Wijaya I Wayan Arta Wijaya I Wayan Arta Wijaya I Wayan Rinas I Wayan Sukerayasa I.W.A Wijaya I.W.A. Wijaya Ida Bagus A. Swamardika Ida Bagus Adisimakrisna Peling Ida Bagus Gede Wira Negara Ida Bagus Made Pandwa Putra IGP Agung Satya Wicaksana INA Seputra IWA Wijaya IWY Swara I_M. Suartika K A Kartika Sari Kadek Mirah Mahadewi Kadek Paramarta Dwi Parna kadek rudi andika setyawan Kadek Widipratama Ketut Dharma Yasa Khana Eland N.A Kharis Biantoro Lie Jasa M.S. Ugustra Made Andi Kusumayana B Made Dinda Pradnya Pramita Ngakan Putu Satriya Utama Ni Wayan Dian Puspita Sukma Dewi Nia Paramitha NPG Suardana Nyoman Karnata Mataram P A Mertasana Putu Quentin MP Putu Sri Merta Suryani Quentin MP, Putu Ravinda Ariestya Pamungkas Riantika, I Gede Rama Rinas, I W. Rukmi Sari Hartati Satcitananda P, I G.B. Satriyo Agung Pribadi Tjok Gede Indra Partha W G Yoga Ananta Wijaya W. Arta Wijaya W.G. Suharthama Wahyu Adi Merta Wayan Gede Ariastina Yanu Prapto Sudarmojo Zulfachmi, Zulfachmi