Peramalan Beban Listrik Kabupaten Cilacap Aruna, Evan Dhia; Fatkhurrozi, Bagus; Kurniawan, Andriyatna Agung
ULIL ALBAB : Jurnal Ilmiah Multidisiplin Vol. 3 No. 2: Januari 2024
Publisher : CV. Ulil Albab Corp

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.56799/jim.v3i2.2813

Abstract

This study examines electricity load, emphasizing the need for accurate prediction and optimal distribution. Utilizing artificial neural networks and the backpropagation algorithm, the research leverages data from BPS Kabupaten Cilacap and PT. PLN (Persero) UP3 Kabupaten Cilacap. Various configurations for hidden layer neurons, epochs, and learning rates are explored to determine the optimal network architecture for forecasting. The selected model, with specific criteria, demonstrates high accuracy during training (MSE: 0.00099999, MAPE: 5.44%, Regression: 0.98226) and testing (MSE: 0.0009493, MAPE: 3.99%, Regression: 0.90709) phases. The conclusion affirms the effectiveness of the Backpropagation ANN method in predicting electricity load in Kabupaten Cilacap for the period 2023-2030, meeting PLN's tolerance of ≤ 10% based on the MAPE criteria.
COMPARATIVE STUDY OF DISTRIBUTED DENIAL OF SERVICE (DDOS) ATTACK DETECTION IN COMPUTER NETWORKS Adam Zukhruf; Bagus Fatkhurrozi; Andriyatna Agung Kurniawan
Jurnal Teknik Informatika (Jutif) Vol. 4 No. 5 (2023): JUTIF Volume 4, Number 5, October 2023
Publisher : Informatika, Universitas Jenderal Soedirman

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.52436/1.jutif.2023.4.5.756

Abstract

Distributed Denial of Service (DDoS) attack is an internet crime that aims to consume server resources so that the server becomes unusable. Suricata, Snort and Wireshark are useful software applications for detecting DDoS attacks. This study aims to compare the performance of the snort, suricata and wireshark applications in detecting Distributed Denial of Service attacks. The comparison parameters used are the total attacks that can be detected and memory usage. The type of attack used in testing is syn flood and ping of death. The research results obtained by Suricata became the most effective application in this study compared to snort and wireshark. Suricata excels in memory usage in the two types of attacks performed with the percentage of memory usage being 0.1891 GB (4.975%) during syn flood attacks and 0.00114 GB (0.03%) during ping of death attacks. Suricata also excels in the percentage of the total number of detected ping of death attacks, namely 86,472%.
Perancangan Pembangkit Listrik Tenaga Surya (PLTS) Atap On-Grid 44 kWp untuk Melayani Beban Penerangan di Industri Wibowo, Kristianto Agung; Pravitasari, Deria; Kurniawan, Andriyatna Agung; Nawawi, Ibrahim
Aviation Electronics, Information Technology, Telecommunications, Electricals, and Controls (AVITEC) Vol 6, No 2 (2024): August
Publisher : Institut Teknologi Dirgantara Adisutjipto

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.28989/avitec.v6i2.2194

Abstract

Saat ini pemerintah terus mendorong masyarakat untuk memanfaatkan EBT di Indonesia untuk mencapai target bauran sebanyak 23 % di tahun 2025. Pada penelitian ini dilakukan perancangan PLTS atap on-grid pada salah satu industri yang bergerak di bidang pengolahan bahan pangan hewani. PLTS digunakan untuk melayani beban penerangan dengan standar kelayakan mengikuti panduan EBTKE ESDM (SNI 8395:2017) dan sistem instalasi pemasangan berdasarkan PUIL 2011. Berdasarkan hasil perancangan digunakanlah modul surya jenis monocrystalline 410 Wp sebanyak 108 unit dan satu unit inverter 40 kW yang menghasilkan energi sebesar 63.032,58 kWh/tahun dan pengurangan emisi gas karbon dioksida (CO2) sebanyak 78.790,725 ton/tahun. Hasil kelayakan ekonomi dengan investasi awal Rp. 548.890.000, menghasilkan NPV Rp. 72.019.012, BCR 1,11, dan payback period pada tahun ke-18. Hasil tersebut menunjukkan bahwa PLTS dapat melayani beban penerangan dan melakukan penghematan energi listrik sebesar penggunaan beban penerangan harian di industri.
Pendampingan Digitalisasi Sistem Pelayanan Administransi Pemerintahan Desa Berbasis Website di Desa Ngargogondo Kecamatan Borobudur Nurhikmahyanti, Desi; Kurniawan, Andriyatna Agung; Setiawati, Rini
Abdimas Galuh Vol 6, No 1 (2024): Maret 2024
Publisher : Universitas Galuh

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.25157/ag.v6i1.12302

Abstract

Tujuan umum program pengabdian tematik berbasis SDGs ini adalah untuk meningkatkan kapasitas aparatur pemerintah desa dalam rangka memperbaiki tata kelola pemerintahan desa dan meningkatkan kualitas pembangunan desa secara berkelanjutan. Tujuan khusus program pengabdian tematik berbasis SDGs ini adalah sebagai berikut. (1) meningkatkan kinerja pemerintah dan aparatur desa melalui peningkatan kapasitas yang berbasis kebutuhan dan permintaan masyarakat; (2) meningkatkan pembangunan partisipatif melalui perbaikan sistem pendampingan dan peningkatan kapasitas masyarakat; serta (3) meningkatkan koordinasi, supervisi, monitoring dan evaluasi kinerja pemerintah desa melalui peningkatan sistem informasi dan data desa berbasis teknologi.   Permasalahan yang dihadapi mitra meliputi aspek manajemen dan teknologi. Solusi permasalahan manajemen: (1) pendampingan pelaksanaan tata kelola pemerintahan desa yang efektif dan efisien, (2) pendampingan pelaksanaan sistem pelayanan administrasi pemerintahan desa. Solusi permasalahan teknologi: (1) pendampingan pengelolaan website desa (2) pendampingan pelaksanaan digitalisasi sistem pelayanan administrasi pemerintahan desa. Metode kegiatan: perencanaan, pelaksanaan, dan evaluasi. Persiapan: sosialisasi program, penetapan tim pelaksana kegiatan, penyusunan modul pendampingan, penyusunan indikator dan instrumen, serta pembekalan teknis. Pelaksanaan: diskusi kelompok, pelatihan, serta pendampingan. Monitoring dan evaluasi:  pendampingan pelaksanaan tata kelola pemerintahan desa, pendampingan pelaksanaan sistem pelayanan administrasi pemerintahan desa yang efektif dan efisien, pendampingan pengelolaan website desa, pendampingan pelaksanaan digitalisasi sistem pelayanan administrasi pemerintahan desa.
The Evaluation of Lighting System Planning based on Green Building Concepts using DIALux Evo Software Rosyad Febrian, Muhammad Dziya'ur; Pravitasari, Deria; Kurniawan, Andriyatna Agung; Setiawan, Hery Teguh
Jurnal Listrik, Instrumentasi, dan Elektronika Terapan Vol 7, No 1 (2026)
Publisher : Departemen Teknik Elektro dan Informatika Sekolah Vokasi UGM

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.22146/juliet.v7i1.113428

Abstract

Building construction contributes to 40% of carbon emissions, while during the operational phase, approximately 50% of energy is used to create an artificial climate, such as lighting systems. This study applies the Green Building concept to the lighting system on the first floor of Building X with the aim of achieving energy savings and reducing carbon emissions. The scope of the study includes the evaluation and improvement of the lighting system design on the first floor of Building X based on Green Building standards in accordance with Minister of Public Works and Public Housing Regulation No. 21 of 2021. The evaluation results show that the lighting system on the first floor of Building X does not fully meet Green Building standards, therefore improvements are needed. Improvements to the artificial lighting system were made by recalculating the lighting requirements, resulting in a 16.62% reduction from the initial plan. Meanwhile, improvements to natural lighting by combining it with artificial lighting resulted in a reduction of up to 61.28%. Therefore, the first floor of Building X supports one of the principles of the Green Building concept, which is the reduction of energy use and carbon emissions.
Voltage Drop and Power Loss Mitigation on SGN-14 via SGN-15 Feeder Design in Distribution System ULP Magelang Haqrodji Prabu Yasya; Deria Pravitasari; Agung Trihasto; Andriyatna Agung Kurniawan
Aviation Electronics, Information Technology, Telecommunications, Electricals, and Controls (AVITEC) Vol 8, No 1 (2026): February
Publisher : Institut Teknologi Dirgantara Adisutjipto

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.28989/avitec.v8i1.3686

Abstract

Feeder SGN-14 of PT PLN (Persero) ULP Magelang operates under overload conditions, significantly degrading voltage quality and increasing technical losses. PLN (Perusahaan Listrik Negara) is Indonesia’s State Electricity Company, while ULP (Unit Layanan Pelanggan) refers to a customer service unit. This study designs Feeder SGN-15 as a 20 kV load-splitting feeder supplied from Sanggrahan Substation and terminating near KH. Maksum Street (Tempuran). The feeder is 20.7 km long and routed close to the load centre to reduce line losses. Network performance is assessed using ETAP load-flow simulations and independent GNU Octave calculations of voltage profile, current, and power/energy losses, referenced to SPLN T6.001:2013 with a 10% voltage-drop limit. The proposed feeder uses 8,152 m of insulated MVTIC and 12,584 m of AAAC conductors, supported by 238 concrete poles, together with required switching devices, line accessories, and four CSP transformers. After reconfiguration, the maximum voltage drops on SGN-14 decreases from 12.82% to 6.5%, while SGN-15 operates at about 4.95%, ensuring all buses comply with SPLN T6.001:2013. Technical losses on SGN-14 fall from 388.711 to 112.337 (W/kWh), and SGN-15 contributes 81.130 (W/kWh), giving total post-reconfiguration losses of 195.467 (W/kWh). The reduction in energy-loss cost yields an estimated saving of Rp228.82 million per month, lowering losses from Rp460.32 million/month to Rp231.44 million/month. Unlike studies that optimize only switch states or voltage-regulator placement, this work shows that adding a new 20 kV feeder can jointly improve voltages, reduce losses, and deliver tangible benefits for the distribution utility.
Numerical Study of Savonius Wind Turbine Performance at Tidar University under Wind Speed and Direction Angle Using the CFD Method Ahmad Izzudin Robani; Nurmala Dyah Fajarningrum; Raka Mahendra Sulistiyo; Fuad Hilmy; Andriyatna Agung Kurniawan
Jurnal Rekayasa Mesin Vol. 21 No. 1 (2026): Volume 21, Nomor 1, April 2026
Publisher : Mechanical Engineering Department - Semarang State Polytechnic

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.32497/jrm.v21i1.7146

Abstract

The savonius wind turbine is a type of vertical axis wind turbine (VAWT) that operates based on the drag force principle. Its simple design, featuring S-shaped blades arranged around a vertical shaft, enables the turbine to capture wind from any direction and operate effectively at low wind speeds, making it suitable for residential areas. This study investigates the performance of a three-bladed helical Savonius turbine with a 180° twist angle under variations in wind speed and wind direction. Numerical simulations were conducted using Computational Fluid Dynamics (CFD). Wind speed data were obtained from rooftop measurements at the Faculty of Economics, Tidar University, recorded at 08:00, 10:00, 12:00, 14:00, and 16:00, with average values of 1.9 m/s, 2.0 m/s, 2.2 m/s, 2.2 m/s, and 2.0 m/s, respectively. The analyzed wind direction angles were 15 , 25 , and 35 . Results show that a 15  wind direction produced the most stable and optimal performance, achieving a turbine power ( ) of 0.0356 W, a power coefficient (Cp) of 0.0931, and a TSR of 0.525. This occurred because the airflow aligned more effectively with the rotor, improving kinetic energy capture, reducing drag flow on the convex returning blade, and minimizing vortex formation and negative torque. Peak performance occurred at 12:00 and 14:00 when wind speeds exceeded 2.0 m/s. However, the power coefficient showed a decreasing trend due to the presence of adverse flow phenomena that reduce the amount of wind energy converted by the turbine.
Analisis Ketidakseimbangan Beban terhadap Kerugian Daya pada Transformator Distribusi 20 kV Menggunakan Software ETAP Maulana Muslimin; Agung Trihasto; Deria Pravitasari; Andriyatna Agung Kurniawan
Jurnal Teknik Elektro dan Komputasi (ELKOM) Vol. 8 No. 1 (2026): Jurnal Teknik Elektro dan Komputasi (ELKOM)
Publisher : Universitas Muhammadiyah Jember

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.32528/elkom.v8i1.4948

Abstract

Abstract - Load imbalance in distribution transformers can lead to an increase in neutral current and power losses, thereby reducing the efficiency of the electric power distribution system. This condition was identified in six 20 kV distribution transformers on the SGN 04 feeder in Magelang, with initial load imbalance levels of 23.02% at M1-35A-2A, 22.7% at M1-44-26-4-A, 12.79% at M1-44-34, and the highest value of 54.33% at M1-44-9. This study aims to analyze the effect of load imbalance on neutral current and power losses and to evaluate the effectiveness of load balancing through inter-phase load relocation. The methods employed include load current measurements conducted over five days, symmetrical component calculations using GNU Octave, and Unbalanced Load Flow simulations using ETAP software to validate the calculation results. The results show that load imbalance has a significant impact on power losses, as indicated by an initial neutral current of up to 148.142 A at transformer M1-44-9 and power losses reaching 21.0245 kW. After load balancing was implemented, all transformers exhibited significant improvement, with load imbalance values reduced to below 3%, for example, M1-35A-2A decreased to 1.33%, M1-44-31 to 1.35%, and M1-44-9 to 0.45%. In addition, the neutral current was significantly reduced, such as at M1-44-9, where it decreased from 148.14 A to 11.84 A, and the remaining power losses were only in the range of 0.0068–0.1343 kW. Therefore, the load relocation strategy is proven to be effective in reducing load imbalance, neutral current, and power losses in accordance with SPLN 17:2014, while also improving the stability of the distribution system. Keywords : Load Imbalance, Distribution Transformer, Power Loss, ETAP, GNU Octave.
Perencanaan Perbaikan Faktor Daya Pada Industri Otomotif Muhammad Fachrul Reza; Deria Pravitasari; Agung Trihasto; Andriyatna Agung Kurniawan
Jurnal Teknik Elektro dan Komputasi (ELKOM) Vol. 8 No. 2 (2026): Jurnal Teknik Elektro dan Komputasi (ELKOM)
Publisher : Universitas Muhammadiyah Jember

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.32528/elkom.v8i2.4618

Abstract

Low of electrical power factor in industry increases power losses and loading still far from the available capacity has the potential to increase operational load. The objective of this research is to improve the power factor and to reduce power losses in all percentages of electrical system load at PT Putra Agung Setia using centralized capacitor bank. The method of research begins with an analysis of load profile data then creation of linear regression functions and alternative loading. Next, capacitor bank planning and power loss calculations are carried out. The results of research show that the lowest and highest loading percentage values when the system experiences power factor problems are 4.388% and 15.038%, then the linear regression model is obtained with the equation y = -1.9273 + 1.6188x. Linear regression model was created with baseline load profile. Alternative load scenarios were defined by 25%, 50%, 75%, and 100% higher than the highest baseline value. All alternative scenarios exhibited low power factor. The increase of power factor was carried out in percentage of loading at 4.388% to 100%. The reference target power factor improvement is set at 1. The results of Capacitor bank planning shows the need values of 2.5 kVAR, 5 kVAR, 10 kVAR, 20 kVAR, 40 kVAR, and 80 kVAR. The results of power factor improvement shows that the average power factor increases, while power losses decrease. The average power factor in the baseline and alternative scenarios increases to near 1, while power losses decrease to near 0 kW.
Analisis Kinerja Relai Diferensial Pada Transformator Daya 60 MVA Gardu Induk Sanggrahan Muhammad Hafizh Haqiqi; Agung Trihasto; Andriyatna Agung Kurniawan; Muhammad Syukron
Jurnal Teknik Elektro dan Komputasi (ELKOM) Vol. 8 No. 2 (2026): Jurnal Teknik Elektro dan Komputasi (ELKOM)
Publisher : Universitas Muhammadiyah Jember

Show Abstract | Download Original | Original Source | Check in Google Scholar | DOI: 10.32528/elkom.v8i2.6353

Abstract

Transformator daya merupakan peralatan utama dalam sistem tenaga listrik yang memerlukan sistem proteksi yang andal untuk menjaga kontinuitas dan keamanan penyaluran energi listrik. Pada transformator daya 60 MVA Unit 4 Gardu Induk 150 kV Sanggrahan, hasil asesmen Through Fault Current (TFC) menunjukkan kondisi waspada sehingga diperlukan evaluasi terhadap kinerja rele diferensial sebagai proteksi utama transformator. Penelitian ini bertujuan menganalisis kinerja rele diferensial melalui perbandingan antara setting eksisting dan setting hasil perhitungan teoritis menggunakan perangkat lunak ETAP 21.0.1. Metode penelitian meliputi perhitungan parameter setting rele diferensial berdasarkan data teknis transformator dan CT serta simulasi kondisi normal, gangguan di dalam zona proteksi, dan gangguan di luar zona proteksi menggunakan ETAP 21.0.1. Hasil perhitungan teoritis diperoleh nilai arus setting sebesar 0,0962 A, arus restrain 0,8179 A, Slope 1 sebesar 11,76%, dan Slope 2 sebesar 23,52%, sedangkan setting eksisting yang digunakan pada rele diferensial yaitu arus setting sebesar 0,3 A, arus restrain sebesar 4 A, Slope 1 sebesar 30%, dan Slope 2 sebesar 80%. Hasil simulasi menunjukkan kedua setting rele diferensial bekerja pada seluruh gangguan di dalam zona proteksi berupa hubung singkat tiga fasa, dua fasa, dan satu fasa ke tanah, serta tetap stabil pada kondisi normal maupun gangguan di luar zona proteksi. Perbedaan nilai setting tersebut disebabkan oleh pertimbangan kondisi aktual sistem, seperti arus inrush, arus eksitasi transformator, kesalahan CT, kesalahan sadapan, mismatch, dan faktor keamanan sesuai standar PLN. Hasil simulasi menunjukkan bahwa setting rele diferensial eksisting yang digunakan telah mampu memberikan proteksi yang baik terhadap transformator daya.